BW Defender2
Calibration and Setting Alarm Setpoints
31
Setting the Remaining Alarm Setpoints
The display shows the Low Alarm setpoint for the next sensor.
The Set up/down arrows lights, prompting you to input a new
Low Alarm setpoint.
6. Repeat steps 3 through 6 to set alarm setpoints for CO,
LEL and O
2
.
After all alarm setpoints are set, the audible alarm beeps four
times and the detector returns to normal operation.
Verification (optional)
Test the detector using a gas cylinder other than the one used
in the calibration steps. The gas concentration should not
exceed the sensor's detection range. Confirm that the display
shows the expected concentration.